Other Ways To Back Up Settings - Siemens SINAMICS G120 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Data backup and series commissioning

10.4 Other ways to back up settings

10.4
Other ways to back up settings
Description
In addition to the default setting, the converter has an internal memory for backing up three
other settings.
On the memory card, you can back up 99 other settings in addition to the default setting.
You will find additional information on the Internet at: Memory options
(http://support.automation.siemens.com/WW/view/en/43512514).
Table 10- 1
Parameter
p0970
p0971
Table 10- 2
Parameter
p0802
p0803
Table 10- 3
258
Backing up settings in the converter
Description
Reset drive parameters
Load backed-up setting (number 10, 11 or 12). You overwrite your actual parameter
setting when loading.
Save parameters
Back up the setting (10, 11 or 12).
Backing up additional settings on the memory card
Description
Data transfer with memory card as source/target (factory setting: 0)
Default setting: p802 = 0
Further settings: p802 = 1 ... 99
Data transfer with device memory as source/target (factory setting: 0)
Default setting: p803 = 0
Further settings: p803 = 10, 11 or 12
Operation on the BOP-2
Description
OK
OK
OK
OK
The converter writes its setting 0, 10, 11 or 12 to the memory
card in accordance with p0802. The file on the memory card is
assigned the number according to p0802.
The converter loads the setting with the number according to
p0802 from the memory card and thus overwrites its setting 0,
10, 11 or 12.
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
SINAMICS G120C frequency converter

Advertisement

Table of Contents
loading

Table of Contents