Siemens SINAMICS G120 Operating Instructions Manual page 316

Frequency converter
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Appendix
A.1 Parameter
Table A- 3
How you select the command source and setpoint sources
Parameter
Description
p0015
Parameter p0015 allows the setting of pre-defined I/O configurations. Further information is given in the
section: Selecting the interface assignments (Page 44).
Table A- 4
This is how you parameterize the up and down ramps
Parameter
Description
p1080
Minimum speed
0.00 [rpm] factory setting
p1082
Maximum speed
1500.000 [rpm] factory setting
p1120
Rampup time
10.00 [s]
p1121
Rampdown time
10.00 [s]
Table A- 5
This is how you set the closed-loop type
Parameter
Description
p1300
0: V/f control with linear characteristic
1: V/f control with linear characteristic and FCC
2: V/f control with parabolic characteristic
3: V/f control with parameterizable characteristic
4: V/f control with linear characteristic and ECO
5: V/f control for drives requiring a precise frequency (textile area)
6: V/f control for drive requiring a precise frequency and FCC
7: V/f control with parabolic characteristic and ECO
19: V/f control with independent voltage setpoint
20: Speed control (without encoder)
Table A- 6
Optimizing starting behavior for V/f control for a high break loose torque and overload
Parameter
Description
p1310
Voltage boost to compensate ohmic losses
The voltage boost is active from standstill up to the rated speed.
It is at its highest at speed 0 and continually decreases as the speed increases.
Value of voltage boost at zero speed in V:
1.732 × rated motor current (p0305) × stator resistance (r0395) × p1310 / 100%
p1311
Voltage boost when accelerating
The voltage boost is effective from standstill up to the rated speed.
It is independent of the speed and has a value in V of:
1.732 × rated motor current (p0305) × stator resistance (p0350) × p1311 / 100%
p1312
Voltage boost when starting
Setting for an additional voltage boost when powering-up, however, only for the first acceleration phase.
314
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB

Advertisement

Table of Contents
loading

Table of Contents