10.3
Saving settings and transferring them using an operator panel
When the power supply is switched on, you can transfer the settings
of the converter to the BOP-2 or, vice versa, transfer the data from the
BOP-2 to the converter.
Procedure converter → BOP-2
Start data transfer in the menu "EXTRAS" - "TO BOP".
Procedure BOP-2 → converter
Start data transfer in the menu "EXTRAS" - "FROM BOP".
Switch off the converter power supply.
Wait until all LED on the converter go dark. Now switch on the
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
converter power supply again. Your settings only become effective
after this power-on reset.
10.3 Saving settings and transferring them using an operator panel
Data backup and series commissioning
OK
OK
OK
OK
257