Backing up data and series commissioning
7.4 Other ways to back up settings
BOP-2 → inverter
Procedure
To transfer the settings to the inverter, proceed as follows:
1.
2.
3.
4.
5.
6.
7.
You have transferred the settings to the inverter.
7.4
Other ways to back up settings
In addition to the default setting, the inverter has an internal memory for backing up three
other settings.
On the memory card, you can back up 99 other settings in addition to the default setting.
You will find additional information on the Internet at: Memory options
(http://support.automation.siemens.com/WW/view/en/43512514).
Table 7- 1
324
Go to the menu level "OPTIONS".
In the "OPTIONS" menu, select "FROM BOP".
Start data transfer with OK.
Wait until the inverter has written the settings to the memory card.
Switch off the inverter power supply.
Wait until all LEDs on the inverter are dark.
Switch on the inverter power supply again.
Your settings become effective after switching on.
Operation on the BOP-2
Description
The converter writes its setting 0, 10, 11 or 12 to the memory
card in accordance with p0802. The file on the memory card is
assigned the number according to p0802.
The converter loads the setting with the number according to
p0802 from the memory card and thus overwrites its setting 0,
10, 11 or 12.
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Converter with CU230P-2 Control Units