In the first step of the Wizard select the control mode.
See also section: Factory setting of the inverter control (Page 55).
Select the default setting the interfaces of the converter.
See also section: Selecting the interface assignments (Page 44).
Select the application for the converter:
Low overload for applications that only require a low dynamic
performance, e.g.: Pumps or fans.
High overload for applications requiring a high dynamic performance,
e.g. conveyor systems.
Select your motor.
Enter the motor data according to the rating plate of your motor.
If you have selected a motor based on its order number, the data is
already entered.
If you have set the "Speed control" control mode, then we recommend
setting "[1] Identify motor data at standstill and with motor rotating".
With this setting, the converter optimizes its speed controller.
In one of the following cases is applicable, select the setting "[2] Identify
motor data at standstill":
 You have selected "Speed control" as control mode, however the
motor cannot freely rotate, e.g. for mechanically limited traversing
sections.
 You have set "U/f control" as control mode.
Set the most important parameters to suit your application.
We recommend the setting "Calculate motor data only".
Set the checkmark for "RAM to ROM (save data in the drive)" to save
your data in the converter so that it is not lost when the power fails.
Close basic commissioning.