Siemens SINAMICS G120 Operating Instructions Manual page 301

Frequency converter
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Table 13- 2
EMC Phenomenon
Conducted emissions
(disturbance voltage)
Radiated emissions
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Conducted disturbance voltage and radiated emissions
Converter type
Remark
All converters with integrated class A filters.
Order number:
6SL3210-1KE**-*A**
1. All converters frame sizes A with integrated
class A filter.
Order number: 6SL3210-1KE1*-*A**
2. The following converters frame sizes B with
integrated class A filter.
Order number:
6SL3210-1KE21-*AB* (USS, MB)
6SL3210-1KE21-*AP* (PROFIBUS)
6SL3210-1KE21-*AC* (CANopen)
3. Converter frame size B
with integrated class A filter,
with PROFINET interface.
Order number: 6SL3210-1KE21-*AF*.
The converter has to be installed with a line
reactor.
In a domestic environment this product may cause
radio interference in which case supplementary
mitigation measures may be required.
1. Converter frame size B
with integrated class A filter,
with PROFINET interface,
Order number: 6SL3210-1KE21-*AF*
In installations without line reactor.
2. Converter frame size C with integrated class A
filter.
Order number:
6SL3210-1KE22-*A**
6SL3210-1KE23-*A**
This type of PDS is not intended to be used in low-
voltage public power supply network which supplies
domestic premises. Radio frequency interference is
expected if used on such a network.
Technical data
13.4 Electromagnetic Compatibility
Level acc. to
IEC 61800-3
Category C2
First Environment -
Professional Use
Category C2
First Environment -
Professional Use
Category C3
Second
Environment
299