Use an unshielded cable for the mains connection of Power Modules with integrated filter.
Power Modules, which are connected to the line supply via an external filter, require a
shielded cable between the line filter and Power Module.
Cables inside the cabinet
● All power cables of the drive (line supply cables, cables to braking resistors, as well as
● Line supply cables running between the supply system and the line filter must be routed
● Signal and data cables, as well as filtered line supply cables, may only cross non-filtered
● All cable lengths must be minimized (excessive cable lengths must be avoided).
● All cables must be routed as closely as possible to grounded housing components, such
● Signal and data cables, as well as their associated equipotential bonding cables, must
● When unshielded single-wire cables are used within a zone, the feed and return lines
● Spare wires for signal and data cables must be grounded at both ends to create an
● Signal and data cables should enter the cabinet only at one point (e.g. from below).
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
motor cables) must be routed separately from signal and data cables. The minimum
distance should be approximately 25 cm / 9.84 in. Alternatively decoupling in the cabinet
can be implemented by means of separation plates connected to the mounting plate
(back plane) with excellent electrical conductivity.
separately from non-filtered power cables (cables to braking resistors as well as motor
cables).
power cables at right angles of 90° to minimize coupled-in interference.
as mounting plates or the cabinet frame. This reduces interference radiation as well as
coupled-in interference.
always be routed in parallel and with as short a distance as possible.
must be either routed in parallel with the minimum possible distance between them, or
twisted with one another.
additional shielding effect.