Defining the analog input function
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755 . Parameter p0755 is assigned to the particular analog input via its index,
e.g. parameter p0755[0] is assigned to analog input 0.
Table 7- 6
CI
p1070 Main setpoint
p1075 Supplementary setpoint
p1503 Torque setpoint
p1511 Supplementary torque 1
A complete list of the connector inputs is provided in the List Manual.
Table 7- 7
Analog input 0 is the source for the
additional setpoint.
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Connector inputs (CI) of the converter (selection)
Significance
Example:
p1075
r0755
755[0]
CI
Significance
p1522 Torque limit, upper
p2253 Technology controller setpoint 1
p2264 Technology controller actual value
With Operator Panel
Set p1075 = 755[0]
Adapting the terminal strip
7.4 Analog inputs
In STARTER
Go online with STARTER and
select "inputs/outputs".
Change the input function via
the corresponding screen
form.
81