PC/PG → inverter
Procedure
To transfer the settings, proceed as follows:
1. Go online with STARTER :
2. Select the button "Download project to target system":
3. To save the data in the inverter, select the "Copy RAM to ROM" button:
4. Go offline with STARTER :
You have transferred the settings.
7.3
Other ways to back up settings
In addition to the default setting, the inverter has an internal memory for backing up three
other settings.
On the memory card, you can back up 99 other settings in addition to the default setting.
Additional information is available in the Internet: Memory options
(http://support.automation.siemens.com/WW/view/en/43512514).
7.4
Write protection
The write protection prevents unauthorized changing of the inverter settings. If you are
working with a PC tool, such as STARTER, then write protection is only effective online. The
offline project is not write-protected.
Write protection is applicable for all user interfaces:
● Operator Panel BOP-2 and IOP-2
● STARTER or Startdrive PC tool
● Parameter changes via fieldbus
No password is required for write protection.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH
Data backup and series commissioning
.
.
7.3 Other ways to back up settings
.
.
293