Functions
9.4 Setpoint sources
9.4.4
Specifying the motor speed via the fieldbus
If you enter the setpoint via a fieldbus, you must connect the converter to a higher-level
control. For additional information, see chapter Configuring the fieldbus (Page 85).
Interconnecting the fieldbus with the main setpoint
Figure 9-17
Most standard frames receive the speed setpoint as a second process data PZD2.
Table 9- 21
Parameter
p1070 = 2050[1]
p1075 = 2050[1]
180
Fieldbus as setpoint source
Setting the fieldbus as setpoint source
Remark
Main setpoint
Interconnect the main setpoint with process data PZD2 from the fieldbus.
Additional setpoint
Interconnect the additional setpoint with process data PZD2 from the fieldbus.