Specifying The Motor Speed Via The Fieldbus - Siemens SINAMICS G120 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Functions
9.4 Setpoint sources
9.4.4

Specifying the motor speed via the fieldbus

If you enter the setpoint via a fieldbus, you must connect the converter to a higher-level
control. For additional information, see chapter Configuring the fieldbus (Page 85).
Interconnecting the fieldbus with the main setpoint
Figure 9-17
Most standard frames receive the speed setpoint as a second process data PZD2.
Table 9- 21
Parameter
p1070 = 2050[1]
p1075 = 2050[1]
180
Fieldbus as setpoint source
Setting the fieldbus as setpoint source
Remark
Main setpoint
Interconnect the main setpoint with process data PZD2 from the fieldbus.
Additional setpoint
Interconnect the additional setpoint with process data PZD2 from the fieldbus.
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB

Advertisement

Table of Contents
loading

Table of Contents