Alarms, faults and system messages
12.4 List of alarms and faults
Number
Cause
A07981
No enabling for rotary
measurement
A07991
Motor data identification
activated
F08501
Setpoint timeout
F08502
Monitoring time, sign-of-life
expired
F08510
Send configuration data not valid
A08511
Receive configuration data not
valid
A08526
No cyclic connection
A08565
Consistency error affecting
adjustable parameters
F08700
Communications error
F13100
Know-how protection: Copy
protection error
F13101
Know-how protection: Copy
protection cannot be activated
292
Remedy
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
Switch on the motor and identify the motor data.
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the monitoring time set (p2044).
Check the PROFINET connection.
Check the PROFINET configuration
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
A CAN communications error has occurred. Check the following:
Bus cable
Baud rate (p8622)
Bit timing (p8623)
Master
Start the CAN controller manually with p8608 = 1 after the cause of the fault
has been resolved!
The know-how protection and the copy protection for the memory card are
active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
Insert a valid memory card.