Parameters for the temperature monitoring
Table 9- 32
Parameter
p0335
p0601
p0604
p0605
p0610
p0640
Additional information on the motor temperature monitoring can be found in function diagram
8016 of the List Manual.
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Setting the monitoring
Description
Specify the motor cooling
0: Self-ventilated - with fan on the motor shaft (factory setting)
1: Forced ventilation - with a separately driven fan
2: Self-ventilated and inner cooling (open-circuit cooling)
3: Forced ventilated and inner cooling (open-circuit cooling)
Motor temperature sensor type
0: No sensor (factory setting)
1: PTC (→ p0604)
2: KTY84 (→ p0604, p0605)
4: Temperature switch
Motor temperature alarm threshold (factory setting 130 °C)
Motor temperature fault threshold (Factory setting: 145 °C)
Setting for KTY84 sensor. The parameter has no significance for a PTC sensor.
Motor overtemperature response
Determines the response when the motor temperature reaches the alarm threshold
p0604.
0: Alarm (A07910), but no response of the motor.
1: Alarm (A07910) and reduction of the current limit (factory setting) - this reduces the
motor speed.
2: Fault (F07011) and shutdown.
Current limit (input in A)
Functions
9.7 Protection functions