Functions
9.9 Application-specific functions
Table 9- 42
Parameter
p1215 = 1
p1216
p1217
r0052.12
p0730 = 52.12
p0731 = 52.12
Table 9- 43
Parameter
p0346
p0855
p0858
p1351
p1352
p1475
218
Control logic parameters of the motor holding brake
Description
Enable motor holding brake
0 Motor holding brake locked (factory setting)
3: Motor holding brake just like the sequential control, connected via BICO
Motor holding brake opening time (factory setting 0.1 s)
p1216 > braking signal relay runtimes + brake release time
Motor holding brake closing time (factory setting 0.1 s)
p1217 > braking signal relay runtimes + brake closing time
"Open motor holding brake" command
Signal source for terminal DO 0
Control motor holding brake via digital output 0
Signal source for terminal DO 1
Control motor holding brake via digital output 1
Advanced settings
Description
Magnetizing time (factory setting 0 s)
During this time the induction motor is magnetized. The inverter calculates this
parameter using p0340 = 1 or 3.
Open motor holding brake (imperative) (factory setting 0)
Close motor holding brake (imperative) (factory setting 0)
Starting frequency of motor holding brake (factory setting 0%)
Setting the frequency set value at the slip compensation output when starting with
motor holding brake.
When the parameter p1351 is set to > 0, slip compensation is automatically
switched on.
Starting frequency for motor holding brake (factory setting 1351)
Setting the signal source for the frequency set value at the slip compensation
output when starting with motor holding brake.
Speed controller torque set value for motor holding brake (factory setting 0)
Setting the signal source for the torque set value when starting with motor holding
brake.
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB