Configuring the fieldbus
8.5 Communication via CANopen
Structure of the SDO protocols
The SDO services use the appropriate protocol depending on the task. The basic structure is
shown below:
Byte 0
● The protocol type is contained in byte 0:
● Bytes 1 and 2 contain the index (SINAMICS parameter number)
● Byte 3 contains the subindex (SINAMICS parameter index)
● Bytes 4 ... 7 contain the data corresponding to the second position of byte 0. In the case
136
Header information
Byte 1 und 2
CS
index
– 2F hex: write 4 bytes
– 2B hex: write 3 bytes
– 27 hex: write 2 bytes
– 23 hex: write 1 byte
– 40 hex: read request
– 4F hex: read 4 bytes
– 4B hex: read 3 bytes
– 47 hex: read 2 bytes
– 43 hex: read 1 byte
– 60 hex: write acknowledgment
– 80 hex: error
of an error, these bytes contain the abort code
n user data
Byte 3
Byte 4 ... 7
sub index
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
length
SINAMICS G120C frequency converter