Configuring the fieldbus
8.4 Communication via RS485
Parameter number
Parameter numbers < 2000 PNU = parameter number.
Parameter numbers ≥ 2000 PNU = parameter number - offset.
Table 8- 23
Parameter
number
0000 ... 1999
2000 ... 3999
6000 ... 7999
8000 ... 9999
10000 ... 11999
20000 ... 21999
30000 ... 31999
Indexed parameters
For indexed parameters, you must write the index number as hex value into the sub-index
(IND bit 7 ... 0).
Parameter contents
Parameter contents can be parameter values or connector parameters. For connector
parameters you need two words. For interconnecting connector parameters please see
section: Interconnecting signals in the inverter (Page 315).
Enter the parameter value in the parameter channel right-justified as follows:
 8-bit values:
 16-bit values: Low word, bits 0 ... 15,
 32-bit values: Low word and high word
Enter a connector parameter right-justified as follows:
 Number of the connector parameter:
 Drive object of the connector parameter:
 The index or bit field number of the connector parameter:
116
Write the parameter number into the PNU (PKE bit 10 ... 0).
Write the parameter number minus the offset into the PNU
(PKE bit 10 ... 0).
Write the offset in the page index (IND bit 15 ... 8).
Offset and page index of the parameter numbers
Offset
Page index
Hex
0
0 hex
2000
80 hex
6000
90 hex
8000
20 hex
10000
A0 hex
20000
50 hex
30000
F0 hex
Low word, bit 0 ... 7,
bits 8 ... 15 are zero.
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10
0
0
0
1
0
0
1
0
0
0
0
1
1
0
1
0
1
0
1
1
1
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Bit 9
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
1
0
0
0
High word
Low word, bits 10 ... 15
Low word, bits 0 ... 9
SINAMICS G120C frequency converter
Bit 8
0
0
0
0
0
0
0