Common Technical Power Data - Siemens SINAMICS G120 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

13.3

Common technical power data

Feature
Line voltage
Input frequency
Minimum line impedance U
Power factor λ
Pulse frequency
Maximum motor cable length
Possible braking methods
Degree of protection
Operating temperature
Storage temperature
Relative humidity
Installation altitude
Shock and vibration
Short Circuit Current Rating
(SCCR)
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Specification
3-ph. 380 V AC... 480 V + 10 % - 20 %
47 Hz ... 63 Hz
1 %
K
0.70
4 kHz
The pulse frequency can be increased in 2 kHz steps. A higher pulse frequency reduces
the permissible output current.
Shielded: 50 m
Unshielded: 100 m
25 m (shielded)
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20, cubicle mounting
-10 °C ... +40 °C
-10 °C ... +55 °C
-10 °C ... +60 °C
-40 °C ... +70 °C (-40 °F ... 158 °F)
< 95 % RH - condensation not permissible
Up to 1000 m above sea level
Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-
1 : 1997
Transport in the transport packaging according to Class 2M3 to EN 60721-3-2 : 1997
Vibration during operation according to Class 3M2 to EN 60721-3-3 : 1995
65 kA
The actual permissible line voltage depends
on the installation altitude
Without choke or output options at 4 kHz switching frequency
To fulfil EMC Category C2 conducted emissions at 4 kHz
switching frequency
Without power derating.
Converter with PROFINET
interface.
Converter with USS, MB,
CANopen or PROFIBUS interface.
At higher installation altitudes, the output power
must be reduced
Technical data
13.3 Common technical power data
The output power must be
reduced, see also section:
Temperature and voltage
derating (Page 305)