Functions
9.4 Setpoint sources
Table 9- 15
Parameter
p1070 = 1050
p1035
p1036
Adapting the behavior of the motorized potentiometer
Figure 9-14
Table 9- 16
Parameter
p1047
p1048
p1040
176
Setting the MOP as setpoint source
Remark
Main setpoint
Interconnecting the main setpoint with MOP.
Motorized potentiometer, increase setpoint (factory setting 0)
Interconnect this signal, for example with a digital input of your choice:
p1035 = 722.1 (digital input 1)
Motorized potentiometer, decrease setpoint (factory setting 0)
Interconnect this signal, for example with a digital input of your choice.
Function chart of motorized potentiometer
Basic setup of motorized potentiometer
Description
MOP ramp-up time (factory setting 10 s)
MOP ramp-down time (factory setting 10 s)
MOP start value (factory setting 0 rpm)
Defines the start value [rpm], which is effective when first switching on the motor.