Advanced commissioning
6.14 Setpoints
Under the following conditions, the inverter switches from the main setpoint to other
setpoints:
● When the technology controller is active and appropriately interconnected, its output
specifies the motor speed.
● When jogging is active.
● When controlling from an Operator Panel or a STARTER or Startdrive PC tool.
6.14.2
Analog input as setpoint source
Interconnecting an analog input
If you have selected a pre-assignment without a function of the analog input, then you must
interconnect the parameter of the main setpoint with an analog input.
Figure 6-34
Table 6- 24
Parameter
p1070 = 755[0]
p1075 = 755[0]
6.14.3
Specifying the setpoint via the fieldbus
Interconnecting the fieldbus with the main setpoint
Figure 6-35
214
Example: Analog input 0 as setpoint source
Setting with analog input 0 as setpoint source
Remark
Main setpoint
Interconnect the main setpoint with analog input 0
Additional setpoint
Interconnect the additional setpoint with analog input 0
Fieldbus as setpoint source
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH