• The recommended distance between the rows for thermal
dissipation and fiber cable connections is 15 to 20 cm.
• When you mount systems that are smaller than 12 modules, leave
room for future expansion and power requirements.
• This installation does not take into account space or power
requirements for the distribution blocks or RPIs.
• If you have six or less modules, install the system in a single row.
Install the controller and modules as shown in the top row of
figure 3 and observe the clearances shown. The clearance
between the bottom of the modules and the floor should be
100 cm minimum.