Rack Requirements - Juniper EX4500 Hardware Manual

Hide thumbs Also See for EX4500:
Table of Contents

Advertisement

WARNING:
electrical surge-suppression devices.
Avertissement Vous devez établir un environnement protégé et convenablement mis
à la terre et utiliser des dispositifs de parasurtension.
Table 23: Site Electrical Wiring Guidelines
Site Wiring
Factor
Guidelines
Signaling
If your site experiences any of the following problems, consult experts in electrical surge suppression
limitations
and shielding:
Improperly installed wires cause radio frequency interference (RFI).
Damage from lightning strikes occurs when wires exceed recommended distances or pass between
buildings.
Electromagnetic pulses (EMPs) caused by lightning damage unshielded conductors and electronic
devices.
Radio
To reduce or eliminate RFI from your site wiring, do the following:
frequency
Use a twisted-pair cable with a good distribution of grounding conductors.
interference
If you must exceed the recommended distances, use a high-quality twisted-pair cable with one
ground conductor for each data signal when applicable.
Electromagnetic
If your site is susceptible to problems with electromagnetic compatibility (EMC), particularly from
compatibility
lightning or radio transmitters, seek expert advice.
Some of the problems caused by strong sources of electromagnetic interference (EMI) are:
Destruction of the signal drivers and receivers in the device
Electrical hazards as a result of power surges conducted over the lines into the equipment

Rack Requirements

You can mount the device on two-post racks or four-post racks.
Rack requirements consist of:
Rack type
Mounting bracket hole spacing
You must provide a properly grounded and shielded environment and use
79