Juniper EX4500 Hardware Manual page 133

Hide thumbs Also See for EX4500:
Table of Contents

Advertisement

Figure 39: Remove Plastic Cover from Terminal Block
DC terminal block
DC terminal
block cover
3. Remove the locking screws from each DC power input terminal, using the screwdriver.
4. Ensure that the power source circuit breaker is open so that the voltage across the DC power source
cable leads is 0 V and that the cable leads do not become active while you are connecting DC power.
5. Verify that the DC power cables are correctly labeled before making connections to the power supply.
In a typical power distribution scheme where the return is connected to chassis ground at the battery
plant, you can use a multimeter to verify the resistance of the –48V and RTN DC cables to chassis
ground:
The cable with very high resistance (indicating an open circuit) to chassis ground is negative (–) and
will be installed on the –48V (input) DC power input terminal.
The cable with very low resistance (indicating a closed circuit) to chassis ground is positive (+) and
will be installed on the RTN (return) DC power input terminal.
CAUTION:
The power source cables might be labeled (+) and (–) to indicate their polarity. There
is no standard color coding for DC power cables. The color coding used by the
external DC power source at your site determines the color coding for the leads
on the power cables that attach to the DC power input terminals on each power
supply.
WARNING:
or drape where people can trip on them.
NOTE:
To supply sufficient power, terminate the DC input wiring on a facility DC source
that is capable of supplying a minimum of 20 A at –48 VDC.
You must ensure that power connections maintain the proper polarity.
Ensure that the power cables do not block access to switch components