Table 67: show chassis environment Output Fields (continued)
Field Name
Field Description
Item
Information about the chassis components: Flexible PIC Concentrators (FPCs)–that is, the line
cards–, Control Boards (CBs), Routing Engines (REs), Power Entry Modules (PEMs)–that is, the
power supplies.
Status
Status of the specified chassis component. For example, if Class is Fans, the fan status can be:
Measurement
Depends on the Class. For example, if Class is Temp, indicates the temperature in degrees
Celsius (°C) and degrees Fahrenheit (°F). If the Class is Fans, indicates actual fan RPM.
2. Issue the command show chassis temperature-thresholds. This command displays the chassis
temperature threshold settings. Following is a sample output on an EX9208 switch. The output is similar
on other EX Series switches.
user@ host> show chassis temperature-thresholds
Fan speed
(degrees C)
Item
Chassis default
Routing Engine 0 70
FPC 3
FPC 5
Table 68 on page 257
lists the output fields for the show chassis temperature-thresholds command.
Output fields are listed in the approximate order in which they appear.
Table 68: show chassis temperature-thresholds Output Fields
Field Name
Item
OK: The fans are operational.
Testing: The fans are being tested during initial power-on.
Failed: The fans have failed or the fans are not spinning.
Absent: The fan tray is not installed.
Yellow alarm
(degrees C)
Normal
High
Normal
48
54
65
80
95
55
60
75
55
60
75
Field Description
Chassis component. You can configure for the threshold information for components such as the chas
display in the output. By default, information is displayed only for the chassis and the Routing Engines
Red alarm
(degrees C)
Bad fan
Normal
Bad fan
55
80
65
95
110
110
65
105
80
65
90
80
Fire Shutdown
(degrees C)
Normal
100
112
110
95
257