Environmental Requirements and Specifications for EX Series Switches

The switch must be installed in a rack or cabinet housed in a dry, clean, well-ventilated, and
temperature-controlled environment.
Ensure that these environmental guidelines are followed:
The site must be as dust-free as possible, because dust can clog air intake vents and filters, reducing the
efficiency of the switch cooling system.
Maintain ambient airflow for normal switch operation. If the airflow is blocked or restricted, or if the
intake air is too warm, the switch might overheat, leading to the switch temperature monitor shutting
down the switch to protect the hardware components.
Table 22 on page 73
provides the required environmental conditions for normal switch operation.
Table 22: EX Series Switch Environmental Tolerances
Environment Tolerance
Switch or
device
Altitude
EX2200-C
No performance
degradation up to
5,000 feet (1524
meters)
EX2200
No performance
(except
degradation up to
EX2200-C
10,000 feet
switches)
(3048 meters)
EX2300-C
No performance
degradation up to
5,000 feet
(1524 meters)
Relative Humidity
Normal operation ensured
in the relative humidity
range 10% through 85%
(noncondensing)
Normal operation ensured
in the relative humidity
range 10% through 85%
(noncondensing)
Normal operation ensured
in the relative humidity
range 10% through 85%
(noncondensing)
Temperature
Normal operation ensured
in the temperature range
32° F (0° C) through 104°
F (40° C) at altitudes up to
5,000 ft (1,524 m).
For information about
extended temperature SFP
transceivers supported on
EX2200 switches, see
Pluggable Transceivers
Supported on EX2200
Switches.
Normal operation ensured
in the temperature range
32° F (0° C) through 113°
F (45° C)
Normal operation ensured
in the temperature range
32° F (0° C) through 104°
F (40° C)
73
Seismic
Complies with Zone
4 earthquake
requirements as per
GR-63, Issue 4.
Complies with Zone
4 earthquake
requirements as per
GR-63, Issue 4.
Complies with Zone
4 earthquake
requirements as per
GR-63, Issue 4.