Table 43: Parts Required for Connecting an EX Series Switch to Earth Ground (continued)
Earthing
Terminal
Switch
Location
EX8216
Two earthing
terminals:
Left side of
the chassis
Rear panel
of the
chassis
NOTE:
You
must use only
one of the
two
protective
earthing
terminals.
EX9204,
Rear panel of
EX9208,
the chassis
and
EX9214
EX9251
Rear panel of
the chassis
Grounding
Cable
Grounding Lug
Requirements
Specifications
2 AWG
Panduit LCD2-14A-Q
(33.6 mm²),
or equivalent
minimum 90° C
—provided
wire, or as
permitted by the
local code
One 6 AWG
Thomas& Betts
(13.3 mm²),
LCN6-14 or
minimum 90° C
equivalent—
wire, or one that
provided
complies with
the local code
12 AWG
Panduit
(2.5 mm²),
LCD10-10A-L or
minimum 90° C
equivalent—
wire, or one that
not provided
complies with
the local code—
not provided
Screws and
Additional
Washers
Information
Two ¼ -20 x
0.5 in. screws
with #¼"
split-washer
—provided
Two #¼" flat
washers—
provided
Two ¼ -20
See
Grounding Cable
x 0.5 in. screws
and Lug Specifications
with #¼"
for EX9200
split-washer—
provided
Two #¼" flat
washers—
provided
Two 10-32
See
Grounding Cable
screws—
and Lug Specifications
provided
for EX9200
125
Switches.
Switches.