Nortel DMS-100 Series Maintenance Manual page 260

Subscriber carrier module-100s
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

7-54 Card replacement procedures
NT6X44
NT6X44
SMS
SMS
(continued)
(end)
16
At the frame
17
18
19
20
21
22
23
297-8231-550 Standard 09.01 August 1998
Return the inactive SMS unit to service by typing
>RTS UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the faulty SMS unit
If RTS
passed
failed
Remove the sign from the active SMS unit.
Send any faulty cards for repair according to local procedure.
Record the following items in office records according to local policy:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 22.
Return to the maintenance procedure that directed you to this procedure. At
the point where a faulty card list was produced, identify the next faulty card on
the list and go to the appropriate card replacement procedure for that card in
this manual.
Obtain further assistance in replacing this card by contacting the personnel
responsible for higher level of support.
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue as
directed.
For further assistance with switch of activity, contact the personnel responsible
for the next level of support.
Note: If the system recommends using the SWACT command with the FORCE
option, consult office personnel to determine if use of the FORCE option is
advisable.
Do
step 17
step 21