Nortel DMS-100 Series Maintenance Manual page 217

Subscriber carrier module-100s
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

b.
Set the POWER switch to the ON position.
If FSP is equipped with
fuses
circuit breakers
16
Press and hold the RESET button for 1 second. Both the converter FAIL LED
and FRAME FAIL lamp on the frame supervisory panel (FSP) will be ON.
Go to step 18.
17
Press the RESET button while setting the circuit breaker to the ON position.
Both the converter FAIL LED and FRAME FAIL lamp on the frame supervisory
panel (FSP) will be ON.
At the MAP terminal
18
Load the inactive SMS unit by typing
>LOADPM UNIT unit_no CC
and pressing the Enter key.
where
unit_no
is the number of the faulty SMS unit
If LOADPM
passed
failed
19
Use the following information to determine what step to go to next in this
procedure.
If you entered this procedure
from
alarm clearing procedures
other
DMS-100 Family SMS Maintenance Manual XPM10 and up
Card replacement procedures 7-11
SMS
Do
step 16
step 17
Do
step 19
step 26
Do
step 25
step 20
NT2X70
(continued)