Connect Power And Ground(S) - Avaya S8700 Installing Manual

With media gateways
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

2
Install the first 2 RM0850HA100 Rectifier Modules (comcode 107793796) into the
second and third slots of the power distribution unit.
If 2 to 3 carriers are installed in the system, install a third rectifier module (N+1).
3
4
If 4 to 5 carriers are installed in the system, install a fourth rectifier module.
The fifth rectifier module slot is reserved for future system growth.
5
Rectifier Module Installation
Figure notes
1
Install Battery Interface Unit into Slot 1
Install Rectifier Modules into Slots 2-5
2
Rectifier Module 3 (in Slot 4)
3
4
Test Points
Main Circuit Breakers
5

Connect Power and Ground(s)

Have a qualified electrician connect and route wires from the AC load center to the dedicated
electrical outlet for the power distribution unit.
1
Connect 1 end of a 6 AWG (#40) (16 mm
terminal block at the bottom rear of the cabinet. See
Wiring Diagram'' on page
Route the cabinet GROUND wire to the AC load center single-point ground and connect.
2
3
Connect each remaining media gateway to the AC load center single-point ground.
Installing an Avaya MCC1 Media Gateway
2
) cabinet GROUND wire to the ground
85.
October 2002
''Typical Media Gateway Grounding
83