7-4. Programming for Analog I/O, A/D Converter, and D/A Converter Boards
- When the A/D converter board is installed
K0 to K999 (0 to 5 V, 0 to 10 V and 0 to 20 mA)
The range of converted digital values
(10 bits resolution of special data registers DT9080 to DT9095)
<A/D Converter Board>
• 0 to 5 V range
1,000
Digital
500
data
(K)
0
Analog input (V)
• 0 to 20 mA range
1,000
Digital
500
data
(K)
0

2. Digital Values of Analog Output

• The digital values are stored in the special data registers (DT9096 to DT9103) by the board number selector of each
board.
• Be sure to use the F0 (MV) instruction to transfer the digital values into special data registers DT9096 to DT9103.
• The data is transferred from the special data registers at the time of I/O update in each scan.
Example: Transfer the digital value of data register DT100
to special data register DT9096 when X1 turns
ON.
• The digital data can be transferred into special data registers DT9096 to DT9103 using NPST-GR Software or FP
Programmer II.
Note:
• When the FP-M control board mode selector is set to the PROG. mode or an error occurs, the analog
output data becomes 0.
144
• 0 to 10 V range
1,000
Digital
data
(K)
2.5
5.0
10.0
Analog input (mA)
500
0
5.0
20.0
X1
10.0
Analog input (V)
F0 MV, DT100, DT9096