Item
Disconnection detection
(Note 1)
The full scale (F.S.) on the accuracy of an analog voltage input range from +1 to +5 V and that of an
analog current input range from +4 to +20 mA are 0 to +5 V and 0 to +20 mA, respectively.
(Note 2)
When a value exceeding the rated value ±2% is set, the output is rounded to a value equivalent to the
rated value ±2%.

11.3.7 Output Specifications of the Analog Output Unit

Output specifications
Item
No. of output points
Output range
(Note 1)
(resolution)
Conversion speed
Exceeding the rated range
Total accuracy
Output impedance (voltage output)
Maximum output current (voltage
output)
Output allowable load resistance
(current output)
Insulation method
Conversion execution / non-
execution channel settings
Clipping function
Scale conversion settings
WUME-GM1H-02
Specifications
Disconnection detection is possible for the following ranges. Possible to
select auto or manual resetting
● 1 to 5 V range (Detection level: 0.7 V or less)
● 4 to 20 mA range (Detection level: 2.8 mA or less.)
Specifications
4ch
Voltage
-10 to +10 V DC (Resolution: 1/64,000)
0 to +10 V DC (Resolution: 1/32,000)
-5 to +5 V DC (Resolution: 1/64,000)
0 to +5 V DC (Resolution: 1/32,000)
+1 to +5 V DC (Resolution: 1/25,600)
Current
0 to +20 mA (Resolution: 1/32,000)
+4 to +20 mA (Resolution: 1/25,600)
50 μs/4ch
Possible to output up to the rated value ± 2%
With the 0 to 20 mA range, the lower limit is not supported for exceeding
the rated range.
±0.2%F.S. or less (at +25℃)
±0.4%F.S. or less (at 0 to +55℃)
0.5 Ω or less
10 mA
500 Ω or less
Between output terminals and internal circuit: Photocoupler and isolated
DC/DC converter
Between channels: Non-nsulated
Possible to make non-converted channel settings.
Upper and lower output limits can be set for digital input values.
Setting range: -32,640 to +32,640
A desired value within the digital input range can be set for the scale
conversion setting value.
Setting range: -32768 to +32767
11.3 Specifications of Expansion Units
(Note 2)
11-19