Panasonic FP-M Hardware Manual page 144

Table of Contents

Advertisement

7-2. A/D Converter Board
Analog range setting
Jumper pin
JP1
JP2
JP3
JP4
Note:
• The jumper pins (JP1 to JP4) are set to position "A" when shipped.
Board number setting
• Analog input data for A/D converter boards are stored in special data registers (DT9080 to DT9095) using the
board number selector as follows.
Board
Selector position
number
No. 0
OFF OFF OFF OFF
ON
1
No. 1
ON OFF OFF OFF
ON
1
No. 2
OFF ON OFF OFF
ON
1
No. 3
ON ON OFF OFF
ON
1
Notes:
• Refer to page 201, "8-7. Special Data Registers", for details about special data registers.
• When two or more A/D converter boards are installed, be sure to configure the board number selector in
order to prevent special data register overlap. The board number selectors are set to board number 0 (all
"OFF" position) when shipped.
• Board number selector upper state is "OFF (
136
Pin position
A
Analog input
B
A
Analog input
B
A
Analog input
B
A
Analog input
B
Converted digital value of analog
input from A/D converter board
No. 0
2
3
4
Converted digital value of analog
input from A/D converter board
No. 1
2
3
4
Converted digital value of analog
input from A/D converter board
No. 2
2
3
4
Converted digital value of analog
input from A/D converter board
No. 3
2
3
4
Selectable range
Channel 3
Channel 2
Channel 1
Channel 0
Input/output
)" and the lower state is "ON (
Voltage input: 0 to 5 V
(Current input: 0 to 20 mA)
Voltage input: 0 to 10 V
Voltage input: 0 to 5 V
(Current input: 0 to 20 mA)
Voltage input: 0 to 10 V
Voltage input: 0 to 5 V
(Current input: 0 to 20 mA)
Voltage input: 0 to 10 V
Voltage input: 0 to 5 V
(Current input: 0 to 20 mA)
Voltage input: 0 to 10 V
Channel
Special data
number
register
0
DT9080
1
DT9081
2
DT9082
3
DT9083
0
DT9084
1
DT9085
2
DT9086
3
DT9087
0
DT9088
1
DT9089
2
DT9090
3
DT9091
0
DT9092
1
DT9093
2
DT9094
3
DT9095
)".

Hide quick links: