Input; Output; Relay Output Type - Panasonic FP-M Hardware Manual

Table of Contents

Advertisement

2-1. Specifications of Control Board and Expansion Board

3. Input

Item
Rated input voltage
Operating voltage range
ON voltage/current
OFF voltage/current
Input impedance
Response time
ON ↔ OFF
Operating mode indicator
Insulation method
Notes:
• Input response time can be changed using the input time filtering function to 1, 2, 4, 8, 16, 32, 64, or 128
ms in unit of 8 inputs. However, for expansion boards, the input response time is fixed at 2 ms (or less).
• The number of ON points must be decreased when the ambient temperature is high (between
40 ˚C/104 ˚F and 55 ˚C/131 ˚F).

4. Output

1) Relay output type

Item
Rated operating voltage
Operating voltage range
Output type
Rated control capacity
Response time
OFF → ON
ON → OFF
Mechanical life time
Electrical life time
Surge absorber
Operating mode indicator
20
24 V DC
20.4 V to 26.4 V DC
19.2 V or less/3 mA or less (19.2 V or less/3.6 mA: C32T series only)
2.4 V or more/1 mA or more
Control board: Approx. 4.8 kΩ
Expansion board: Approx. 4.4 kΩ
2 ms or less (at normal input) (See note.)
50 µs or less (in setting high-speed counter)
200 µs or less (in setting interrupt input)
500 µs or less (in setting pulse catch)
LED
Optical coupler
100
Number of ON
points/common [%]
50
0
Ambient temperature [˚C (˚F)]
24 V DC
22.8 V to 26.4 V DC
Normally open (1 Form A), 2 points/common
2 A 250 V AC, 2 A 30 V DC (resistive) (See note 1.)
8 ms or less
10 ms or less
7
2 × 10
operations or more
5
10
operations or more
None
LED
Description
40 (104) 55 (131)
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents