Panasonic FP-M Hardware Manual page 149

Table of Contents

Advertisement

Analog range setting
Jumper pin
Pin position
JP1
JP2
Note:
• The jumper pins (JP1 and JP2) are set to position "A" when shipped.
Board number setting
• Analog output data for D/A converter boards are stored in special data registers (DT9096 to DT9103) using the
board number selector as follows.
Board
Selector position
number
No. 0
OFF OFF OFF OFF
ON
1
2
No. 1
ON OFF OFF OFF
ON
1
2
No. 2
OFF ON OFF OFF
ON
1
2
No. 3
ON ON OFF OFF
ON
1
2
Notes:
• Refer to page 201, "8-7. Special Data Registers", for details about special data registers.
• When two or more D/A converter boards are installed, be sure to configure the board number selector in
order to prevent special data register overlap. The board number selectors of the D/A converter board are
set to board number 0 (all "OFF" position) when shipped.
• Board number selector upper state is "OFF (
A
Analog output
B
A
Analog output
B
Input/output
Digital value for specifying analog
output from D/A converter board
No. 0
3
4
Digital value for specifying analog
output from D/A converter board
No. 1
3
4
Digital value for specifying analog
output from D/A converter board
No. 2
3
4
Digital value for specifying analog
output from D/A converter board
No. 3
3
4
)" and the lower state is "ON (
7-3. D/A Converter Board
Selectable range
Channel 0
Voltage output: 0 to 5 V
(Current output: 0 to 20 mA)
Voltage output: 0 to 10 V
Channel 1
Voltage output: 0 to 5 V
(Current output: 0 to 20 mA)
Voltage output: 0 to 10 V
Channel
number
0
1
0
1
0
1
0
1
)".
Special data
register
DT9096
DT9097
DT9098
DT9099
DT9100
DT9101
DT9102
DT9103
141