1 Power supply connector:
2 Expansion power supply
connector:
3 Input connector (20-pin):
4 Output connector (16-pin):
5 Programming tool port (RS232C):
6 Baud rate selector (9600/19200):
7 Expansion connector:
8 Potentiometers (V0 and V1):
9 Mode selector
(RUN/REMOTE/PROG.):
@ Operation monitor LEDs
(RUN/PROG./ERR./ALARM):
A User memory socket
(EPROM/EEPROM):
B Memory selector
(EPROM/EEPROM):
C Backup battery holder:
D Input indicators (LED):
E Output indicators (LED):
F RS232C port (C20TC type only):
Power supply connector for 24 V DC
Supplies the power (24 V DC) to the expansion board using expansion
power supply cable.
Connects the input field devices (e.g., limit switch).
MIL connector is used. Use a terminal, wire-press socket and flat cable
connector for wiring.
C20T and C20TC types: 12 input points
Connects the output field devices (e.g., solenoid).
MIL connector is used. Use a terminal, wire-press socket and flat cable
connector for wiring.
C20T and C20TC types: 8 output points
Use this port for the programming tools (e.g., FP Programmer II or
personal computer).
Selects the baud rate for communication with a programming tool.
Set the selector according to the connected programming tools.
- FP Programmer (AFP1112): 19,200 bps
- FP Programmer (AFP1112A): 19,200 bps or 9,600 bps
- FP Programmer II (AFP1114): 19,200 bps or 9,600 bps
- Personal computer: 9,600 bps
Connects the expansion boards.
Set with a screwdriver, the potentiometers allow manually adjusting the
controller. This feature makes input an analog value ranging from K0 to
K255. Each set value is stored respectively in manual dial-set registers
(V0: DT9040 and V1: DT9041).
RUN mode:
The control board executes programs.
REMOTE mode:
The RUN or PROG. mode can be changed using
programming tools.
PROG. mode:
Used for editing program.
RUN LED ON:
Turns on when program is executed.
Flashes:
Turns on when forced ON/OFF operation is
executed in RUN mode.
PROG. LED ON:
Turns on when the control board halts program
execution.
ERR. LED ON:
Turns on when a self-diagnostic error occurs.
ALARM LED ON: Turns on when an abnormality is detected or
watchdog timer error occurs.
Use this socket to install the memory (EPROM) and master memory
(EEPROM).
Select the used memory type.
EPROM:
memory
EEPROM: master memory
Holder for the backup battery. Refer to page 125, "6-4. Maintenance", for
details about backup battery replacement.
Indicates the input ON/OFF states.
X0 X1 X2 X3 X4 X5 X6 X7 X8 X9 XAXB
Indicates the output ON/OFF states.
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7
Use this port to connect peripheral devices with RS232C port
(e.g., I.O.P. and bar-code reader).
2-2. Parts Terminology
X0, X4, and X8 LEDs: green
Other LEDs: red
Y0 and Y4 LEDs: green
Other LEDs: red