Panasonic FP-M Hardware Manual page 199

Table of Contents

Advertisement

Address
Name of system register
34
Constant value settings
for scan time
400*
High-speed counter
mode settings
Note:
• * When system registers 400, 402, 403, 404, and 405 are set at the same time, their priorities are:
-1st
400 (high-speed counter mode settings)
-2nd
402 (pulse catch input function settings)
-3rd
403 (interrupt trigger settings)
-4th
404 (input time filtering settings)
-last
405 (input time filtering settings)
Default
value
K0
This register specifies the constant scan time.
• Setting range
K0: the constant scan function is not used (normal)
K1 to K64:
(set value: K1 to K64) × 2.5 ms [2.5 ms to 160 ms]
Note:
• When you set this register using NPST-GR Software, set
a time that can be divided by 2.5.
H0
H0
0
Setting
Set
value
H0
H1
H2
H3
H4
H5
H6
H7
H8
Setting for pulse output connection
H0: Internally not connected
H1: Internally connected
• Output pulse internal connection setting:
Available for transistor output type FP-Ms (C20T, C20TC,
C32T, and C32TC).
• If you are using is the transistor output type FP-Ms, the pulses from
Y6 and Y7 can be directly input to X0 and X1 without external
wiring. However, if X0 and X1 are used as inputs for pulses from
Y6 and Y7, they cannot be used as other input terminals.
Set
value
H107
H108
Description
Input contact of FP-Ms
X0
X1
High-speed counter function not used.
2-phase input
2-phase input
Up input
Up input
Down input
Down input
Up/Down input
(X0: Up input, X1: Down input)
Up/Down input
(X0: Up input, X1: Down input)
Operation mode
Pulse output Y7 → Up input X0
Pulse output Y6 → Down input X1
X2 is not used for high-speed counter
Pulse output Y7 → Up input X0
Pulse output Y6 → Down input X1
X2 is used as reset input
8-5. System Registers
X2
Reset input
Reset input
Reset input
Reset input
191