When an ERR. LED is ON
<Condition: an error is detected by the self-diagnostic function>
Set the mode selector of the FP-M
control board from RUN to PROG.
Is ERR. LED on the
FP-M control board turned
OFF?
YES (ERR. LED OFF)
Probably a total-check error.
Check the program using the
programming tool.
Correct the program referring to page 123,
1. Table of Total-check Error Codes.
Set the mode selector of the FP-M
control board from PROG. to RUN.
NO (ERR. LED ON)
• Using NPST-GR Software Ver. 3.1
<If you are using MENU 1 screen type>
Open [NPST MENU] by pressing
Esc , and then select
"CHECK A PROGRAM" to skip to the
[CHECK A PROGRAM] subwindow.
In the [CHECK A PROGRAM]
subwindow, select "1. TOTALLY
CHECK A PROGRAM".
In the [TOTALLY CHK] window, press F1 to execute the program check.
You can get the address and program where a total-check error occurs. The type of
errors can also be displayed.
• Using FP Programmer II
Press the keys on the FP Programmer II
as shown on the right.
When a total-check error occurs, the
screen shown on the right is displayed.
You can find the address and program
where a total-check error occurs by
pressing the
key.
READ
6-2. Troubleshooting
Go to page 116
<If you are using MENU 2 screen type>
Open [ONLINE MONITOR
FUNCTION MENU] by pressing
Esc , and then select
"V. TOTALLY CHECK".
(–)
READ
ACLR
9
ENT
OP
OP-
9
54PAIR
54PAIR
55SYNTAX
115