3.2.14

Remote access via network connection

Fundamentals
Two networks are optionally available to connect to the higher-level process control system
(PLC, S7, ...). With the drive in the remote mode, a check is made as to whether the network
interface can be controlled.
Network
1
2
Test procedure
1. The network cable is inserted in the interface.
2. The drive is switched into the remote mode using the "Local-Remote switch".
3. The following operating states are set and monitored at the test station via network:
Result
The test is passed if the drive responds as described.
3.2.15

Mechanical door interlock

Fundamentals
The door interlock system locks are tested. The primary key allows access to one or several
secondary keys. The primary key can only be removed if all of the secondary keys are in the key
exchange unit.
Test procedure
1. All drive doors have been closed and interlocked.
2. The locks are locked using the secondary keys.
3. The secondary keys are withdrawn.
SINAMICS PERFECT HARMONY GH180 6SR41 F03 F04 F06 F14 F28 F48 F68 F72 F79 G21 K20 K21 K29 L29 L50 L55 L81 L82 L95 M61
N30 N35 N44 N75 M08 U10 Y15
Reference Manual Rev.201902141441 GH180
Option
G21
G22
G28
G91
G31
G32
G38
G93
– Drive on
– Drive off
– Reset fault
Network version
Mod Bus Plus
Mod Bus RTU
Mod Bus Ethernet
Profi Bus DP
Mod Bus Plus
Mod Bus RTU
Mod Bus Ethernet
Profi Bus DP
Tests
3.2 Function test
27