Four-Feed Pdu - Avaya 1000M Installation And Commissioning Manual

Communication server
Hide thumbs Also See for 1000M:
Table of Contents

Advertisement

Four-Feed PDU

Figure 41
Standard two-feed wiring
Cable-tie saddle
The Four-Feed PDU (NT4N49AA) supports independent power feeds to each
of four modules in a stack if required. However, in a typical installation where
independent power feeds are not required, two jumper wires are provided to
jumper adjacent battery leads. When the jumper wires are used, the four-wire
PDU effectively provides the same "shared" power configuration provided
by the existing DC PDU. Therefore, the new PDU is backward compatible
and can replace an existing PDU unit in a stack, if required.
The NT4N49AA DC PDU:
supports four input circuits, implemented through the following terminal
configuration: four (negative) battery leads, four return leads, and logic
return lead
is fully backward compatible with the existing PDU it is replacing
supports independent power feeds to each of four modules
Installing DC power