Figure 38
Typical installation of the power system frame ground lead
NN43021-310
Standard 06.01
Installing DC power
2
Connect the other end of the cable to the FG collector with a parallel tap
connector, as shown in the left side illustration of Figure 38 on
Continue with step 4.
3
Connect the other end of the cable to the nearest floor ground bar (FGB),
which in some sites may be the building principal ground (BPG), as shown
in the right side illustration of Figure 38 on
4
Repeat step 1 for any other frames as applicable.
5
Secure the cables as required and use an identification tag with the
"
wording
PWR PLT FG
connection.
Candeo power
system
framework
March 2013
page
"
to identify the cables at the BPG or FGB
End of Procedure
page
118.
118.
Candeo power
system
framework
553-AAA1515