Cabling lines and trunks
Procedure 38
Cabling an IPE Module (NT8D37) or Media Gateway
1
Select an appropriate number of NE-A25B (or equivalent) cables long
enough to run from the I/O panels on the rear of the module or backplanes
of the Media Gateway or Expander, to the MDF.
Figure 105 on
page 249
Module.
2
To both ends of each cable, attach a tag that shows the module or chassis
number and the I/O or backplane connector designation.
3
Connect each cable to the appropriate connector on the I/O panel or
backplane, and run the cables to the MDF.
4
Terminate each cable on the cross-connect block designated with the
appropriate module or chassis number.
Note: For information about the MDF layout see "Planning and
designating a Main Distribution Frame" on
5
Make sure all cables are neatly run, properly seated, and secured with
cable ties.