Installing earthquake bracing
Next, each column must also be secured to the floor. This is accomplished by
installing one of two available anchor kits. Select the anchor kit by comparing
the site requirements to Table 60 on
anchor kit can be used to meet the CALIFORNIA OSHPD specification, but
only Kit B meets the BELLCORE specification. For those installations where
neither specification is required, Kit A is recommended due to its shallower
concrete requirement.
Both anchor kits can be used in hardrock concrete as long as the compressive
strength exceeds 20.7 MPa (3000 psi). Only Kit A can be used in lightweight
aggregate concrete with a compressive strength greater than 27.6 MPa
(4000 psi). The floor parameters for your installation can usually be found in
the engineering building drawings.
Table 60
Seismic Anchor Kit
Seismic
Kit
Anchor Kit
A
NT8D64BE
B
NT8D64CE
The kits listed in Table 60 on
mounting hardware. You have the option of purchasing the contents directly
from the manufacturer (using the listing below) or ordering the kits directly
from Avaya.
Kit A (NT8D64BE) contains four of each of the following items:
— Hilti HDI 3/4 in., box of 25, manufacturer part # 457564 (Hilti
Corporation (918) 252-6000) or Multi-Set II, manufacturer
part # RM-34 (ITW Ramset/Redhead, Incorporated (219)
874-4217)
— Hex head bolt, 3/4 in. -10 x 1.50" long, steel material, zinc plate
finish
March 2013
page
330. This table shows that either
CAL
BELLCORE
OSHPD
No
Yes
Yes
Yes
page 330
contain commercially available
Concrete
Light-
thk (min)
weight
90 mm
Yes
(3.5 in.)
180 mm
No
(7 in.)