Page 106 of 436
NN43021-310
Standard 06.01
Installing DC power
capacity of the supplementary shelf is 180 A (six rectifiers delivering 30 A
each), but the sixth rectifier is for N+1 redundancy and kicks in only if one of
the other rectifiers fails.
System Manager SP
The System Manager SP is the advanced controller available with the Candeo
SP power systems. The operational features of the System Manager SP are as
follows:
•
graphical LCD screen
•
local alarm display by means of LED indicators
•
eight programmable alarm outputs (dry-C contacts), with Minor, Major,
and Observation being the factory defaults for outputs 1, 2, and 3
•
eight programmable alarm inputs
•
several processed alarms
•
alarms and events history files
•
alarm management
•
built-in web server
•
Ethernet (LAN) and modem (RS-232) access
•
four levels of access security (one hardware and four passwords)
•
battery database
•
temperature compensation
•
voltage boost (equalize)
•
battery discharge test
•
charge control
•
delivered DC power calculation
•
CAN protocol communication with up to 30 modules
•
maintenance of an inventory of the units in the system
•
field replaceable without interruption of the rectifiers
March 2013