Avaya 1000M Installation And Commissioning Manual page 100

Communication server
Hide thumbs Also See for 1000M:
Table of Contents

Advertisement

Page 100 of 436
NN43021-310
Standard 06.01
Installing DC power
Note 2: The Large Candeo system generally requires one input
receptacle for each rectifier, within 1.8 m (6 ft) of each rectifier. The
commercial power receptacles required are determined by the number
and type of rectifiers used.
Note 3: The Small Candeo system requires two 30 A feeds for each
rectifier shelf, with each shelf supporting five or six rectifiers.
In a single frame configuration, a Candeo system can power a complete range
of medium-sized applications.
Large Candeo: Built around the shelfless Candeo Rectifier 50/48, this
system operates from any voltage between 80 V AC to 300 V AC (single
phase). When configured with 50 A Candeo rectifiers, the system
delivers up to 500 A from a single 1.05 m (42 in.) frame and up to
1000 A from a single 2.1 m (84 in.) frame.
Small Candeo: Built around the Candeo Rectifier 30/48, this system
operates from any voltage between 75 V AC to 310 V AC (single phase).
When configured with 30 A Candeo rectifiers, the system delivers up to
150 A from a single rectifier shelf and up to 300 A from a system
equipped with a supplementary rectifier shelf. The Small Candeo system
comes in 1.3 m (51 in.) and 2.1 m (84 in.) versions.
More detailed information is supplied in the following Candeo power system
manuals, which are included with the system and also available on the Partner
Information Center web page:
Candeo MP481200 Power System User Manual (P0914425)
Candeo MP481200Power System Installation Guide (P0914426)
Candeo SP 48300 Power System User Manual (P7000154)
Candeo SP 48300 Power System Installation Manual (P7000289)
Candeo SP 48300 Power System Quick Installation Guide for Meridian
1 and Avaya Communication Server 1000 Systems (N0029343)
March 2013

Advertisement

Table of Contents
loading

Table of Contents