Configuration
Name/function
Ext DC Fault Reporting
Ext DC Fault Delay
(minutes)
90
Explanation (checkbox)
Activated
Reports that a fault has occurred with the external DC power supply.
Deactivated
Function not possible.
Delay time in minutes (0
If a DC Fault occurs the alarm panel displays an error message after a
few seconds, "General Fault" outputs activate and a log book entry is created
(Mandatory Events).
Power disruptions that last less than 9 s are not reported.
If the power supply is restored within these 9 seconds, the "General Fault" outputs
are reset and a log book entry is created: "Power supply restored".
If the power disruption lasts longer than 9 s, the following occurs:
• If the value is set to 0 min, a warning tone is sounded after 10 s and the alarm
panel reports the failure. "DC Fault" outputs are activated.
• If the value is set to higher than 0 min, this timer is started 10 s after the
disruption occurs.
If the power supply is restored before the end of the set delay time, "General Fault"
outputs are reset and a log book entry is created about the power restore.
No errors are reported.
If the fault still exists after the end of the configured time, a warning tone sounds
and the error is reported. "DC Fault" outputs are activated.
A user can stop the warning tone by entering their code. The alarm panel display
shows details of the warning. "General Fault" and "DC Fault" outputs remain
activated.
If the fault has been corrected, the alarm panel deactivates the "DC Fault" outputs
and creates a log book entry about the power restore. A user can reset the alarm
and the "General Fault" outputs after entering their user code.
60 minutes) until the message is sent.