Function
Zone Resistances
Panel PSU
Meaning
The current resistances for the wired zones are displayed here.
The zone names are displayed. To view the zone numbers, press the right menu key.
Test all variants according to the type of wiring to determine whether they meet the
requirements:
• Alarm contact open/closed
• Tamper contact open/closed
• Short circuits
• Open (isolated circuits)
0k00 means 0 ohms or NC
For wiring type "4-wire CC" the display switches between the resistance of the
alarm loop (A) and the resistance of the tamper loop (S).
Example for a "2-wire FSL 2K2/4K7" zone
• Alarm contact closed (standby)
• Alarm contact open
• Alarm contact open and series resistor bridged 4k68
• Short circuit in line to detector
• Line disconnection
Here you can find information about the voltage values of the power supply:
Ext. DC Voltage In
• The voltage value of the external DC power source
Panel Battery 1
• The voltage value of the first battery
Panel Battery 2
• The voltage value of the second battery
Aux. Voltage Out
• The voltage value at the terminal clamp 0 V/12 V AUX
Example (battery 2 is not connected in this example)
• Ext. DC Voltage In
• Panel Battery 1
• Panel Battery 2
• Aux. Voltage Out
2k18
6k89
0k00
NO
14.1 volts
8.3 volts
0.1 volt
13.9 volts
Configuration
151