Abus SECVEST Installer Manual page 67

Hide thumbs Also See for SECVEST:
Table of Contents

Advertisement

Type
Zone Follow
User Defined
Courtesy Light
Installer on Site
Walk Test
Smoke Sensor Reset
Explanation
This output follows the status of a zone.
If this type is selected, an overview of the zones is provided.
Select a corresponding zone.
This zone can be controlled remotely via different user-
defined components such as remote control or code keypad.
The output can also be assigned a time at which it should
be activated or deactivated.
If this output type is selected, the time at which the output
is activated or deactivated again can be entered in the
connection.
This output is activated while the entry/exit delay time is
running and deactivated 10 seconds after the entry/exit
delay time has expired.
The output is activated as soon as the alarm panel is in
installer mode and deactivated as soon as the installer
has successfully exited this menu.
The output is activated when a user starts a walk test both
as an installer and as a normal user.
The output is also activated in the time between an alarm
being muted and the alarm confirmation.
This output is always activated (0 V) except when a user
confirms a fire alarm.
After this confirmation, the alarm panel deactivates the
output for 3 seconds.
The output type is designed to facilitate interaction with
low voltage reset connections on wired smoke detectors.
Note that there are also smoke detectors common on the
market that require a second confirmation in order to be
reset (detectors that require time to reset the alarm
contacts after the reset pulse).
Configuration
Can be assigned
to partitions
No
No
Yes
No
No
Yes