Configuration
Name/function
Supervision
102
Explanation (checkbox)
Dropdown selection field for alarm system response for supervision
If a wireless detector has had no contact with the alarm panel for more than 20 min,
the alarm panel creates a log entry: "RF warning". The alarm panel also prevents
the system from being armed. If a user overrides this warning and arms the alarm
panel, the log entry "RF warning overridden" is generated.
If a wireless detector has had no contact with the alarm panel for more than 2 h,
corresponding processes are activated as follows:
Alarm panel is armed
Disabled
No response
• Log book entry of this event
Fault
• No display and no warning
tones
• "RF Supervision" or "RF Fault"
outputs are activated
• Tamper alarm
Tamper
• Supervision is reported
Note:
If "Tamp as Tamp-Only" is
disabled, the "Supervision" or
"Fault" outputs are also activated.
If no tamper channel is assigned
in FF, an "unconfirmed alarm"
is sent.
Note
The "Tamper" option is required in Grade 2 systems in order to comply with
EN 50131-1:2006+A1:2009.
If the "Tamper" option is used along with the following setting:
System -> User Reset -> System Tampers = No
the user cannot reset the system.
Alarm panel is disarmed
No response
• Log book entry of this event
• Display and warning tones
• "RF Supervision" or "RF Fault"
outputs are activated
• Tamper alarm
• Supervision is reported
Note
If "Tamp as Tamp-Only" is
disabled, the "Supervision" or
"Fault" outputs are also activated.
If no tamper channel is assigned
in FF, an "unconfirmed alarm"
is sent.