Abus SECVEST Installer Manual page 73

Hide thumbs Also See for SECVEST:
Table of Contents

Advertisement

Name/function
Settle Time
Exit Time [s]
Entry Time [s]
Alarm Response
Siren Delay
Explanation
This option only appears for modes "Final Door Set", "Lock Set" and "Exit Terminate".
Use this option to define a time delay so that detectors can settle before the partition
is armed. This may be necessary if detectors have triggered, send an alarm signal
and have still not been reset. During this time the alarm panel ignores alarm signals
from detectors and sirens are not triggered. Enter the time in seconds as a 2-digit
number: 01
30. The factory default for the settle time is 15 s. In this time the
wireless PIRs located at the exit which have triggered can settle and be reset.
This option only appears for modes "Timed Set" and "Silent Set".
Time for the exit delay in seconds
The exit time can be any value between 10 s and 120 s.
Time for the entry delay in seconds
The entry time can be any value between 10 s and 120 s.
Select the response here for when an alarm occurs in this partition.
Internal
• Alarm panel, indoor siren, info module and control device.
Siren
• Alarm panel, indoor siren, info module and control device.
• External Sirens.
Siren + Comms
• Alarm panel, indoor siren, info module and control device.
• External Sirens.
• Communications.
A siren delay only goes into effect for alarm response "Siren + Comms".
Time for the delay duration of the siren(s).
The siren delay can be set to a value between 0 and 10 min.
When an alarm has been triggered the alarm panel waits until this time has expired
before it activates the sirens.
Note
The siren delay only goes into effect when the alarm response includes comms.
The siren delay does not go into effect when a comms fault occurs.
The siren delay does not go into effect when "Installer Mode->System-
>Confirmation->Confirmation Mode->DD243 or BS8243" and "Installer Mode-
>System->Confirmation->Siren On ->Unconfirm" are set.
If sounders are assigned to multiple partitions, the alarm panel uses the shortest
siren delay set for the partitions in question.
Configuration
73