Configuration
Type
Unset Complete
Zone Omit (Setting)
Zone Omit (System)
Entry Exit Follow
Lockset Unlocked
Open/Close
66
Explanation
The output is activated as soon as the system is disarmed
or deactivated after an alarm.
The output is activated for approx. 10 seconds.
This output is activated when the user omits a zone while
arming the system.
The output is deactivated as soon as the alarm panel
resets the zone.
(Output only functions when confirmation mode DD243 or
BS8243 is selected.)
When there is an unconfirmed alarm the alarm panel
rearms when the confirmation time has expired.
When the zone that triggered the unconfirmed alarm is
still open at the time of rearming, the alarm panel omits
this zone and activates this output.
The alarm panel restores the zone and resets the output
when a user or installer resets the system.
This output is activated for the duration of the delay time
(entry delay or exit delay).
The output is not activated if the partition has been
configured in "Instant Set" or "Silent Set" mode.
A zone lock exists.
The alarm panel activates the output as soon as a zone
with type "Zone Lock" is triggered and deactivates the
output when the zone is closed.
The output is activated when the system (or partition) is
disarmed.
It is deactivated when the system (or partition) is armed.
If this output is assigned to more than one partition, it is
deactivated as soon as one of these partitions is armed or
internally armed.
Note: the function of this output is already inverted by
default compared to the other outputs.
There are 0 volts at this output when the system is
disarmed.
Can be assigned
to partitions
Yes
Yes
Yes
No
Yes