Enabling Memory Transfer Using The Keypad; Panel To Pc Memory Transfer Using Dl900 Software - GE NetworX V3 Installation Manual

Alarm system
Table of Contents

Advertisement

246
NetworX Version 3 Installation Manual
To program the NX-586E using the NX-1048 keypad, select Installer Menu>NX-586E Direct
Connect Module. To program the NX-586E using a PC, start the DL900 up/download software on
the PC.
Note: It is recommended to up/download data when the keypad is in the operating mode only (not in the
programming mode). If you are in the Installer Menu the keypad can time out and start copying process
which will interfere with or stop up/downloading in progress.

Enabling memory transfer using the keypad

The following example uses the NX-1048 keypad to copy the control panel's programming memory
to the NX-586E programming memory 2. It then copies programming information from the NX-
586E programming memory 3 to the control panel.
Navigate with the
1.
To write information from the control panel to the NX-586E, scroll to File 2>Panel to
2.
File and press OK.
Select Yes to confirm and press OK.
3.
The control panel's programming memory is copied to the NX-586E direct connect
4.
module's programming memory 2. The Receiving Data LED on the NX-586E direct
connect module flashes while the data is received. The keypad sounder chimes when the
operation is successful.
To read information from the NX-586E to the control panel, scroll to File 3>File to
5.
Panel and press OK.
Select Yes to confirm and press OK.
6.
The information in the NX-586E programming memory 3 is copied to the current control
7.
panel. The Sending Data LED on the NX-586E direct connect module flashes while the
data is received. The keypad sounder chimes when the operation is successful.
A triple beep sounds if any error occurs when reading or sending data.
8.

Panel to PC memory transfer using DL900 software

Start the DL900 upload/download software.
1.
Select: Program>Setup>Direct Connect Settings.
2.
Select the correct port number and baud rate. Protocol must be Binary (default). The baud
3.
rate should match the NX-586E. Default is 9600. Click OK.
Select the account to use.
4.
Select Download>Direct Connect.
5.
Note: You can also use the tool bar or the [F11] key.
Download as normal. You cannot perform the following:
6.
View keypad status
Enroll devices
keys to NX-586E Direct Connect Module>Files and press OK.