Ac And Dc Server Environmental Requirements; Acoustic Noise Emissions - Sun Oracle Netra SPARC T3-1 Installation Manual

Hide thumbs Also See for Netra SPARC T3-1:
Table of Contents

Advertisement

"Assembling and Connecting DC Power Cords" on page 71

AC and DC Server Environmental Requirements

Caution – Netra rack mounted servers are certified to meet these worst-case
operating conditions only when using an approved rackmount kit. You must strictly
follow the rackmounting instructions in order to meet these environmental
specification.
Specification
*
Ambient temperature
Relative humidity
Elevation
(Company requirement)
Elevation
(NEBS requirement)
* Does not apply to removable media devices.
† Maximum ambient operating temperature is derated by 1 degree C per 500m elevation.
Related Information
"Acoustic Noise Emissions" on page 10
"Cooling Zones and Airflow Clearance" on page 11

Acoustic Noise Emissions

The declared noise emissions for the server are in accordance with ISO 9296
standards.
10
Netra SPARC T3-1 Server Installation Guide • August 2013
Operating
Maximum: 41˚F to 104˚F (5˚C to 40˚C) up to
6000 feet (1829 meters)
Optimal: 69.8˚F to 73.4˚F (21˚C to 23˚C)
Short term maximum: 23˚F to 131˚F (-5˚C to 55˚C)
Operating: 5% to 85% noncondensing, 85˚ (27˚C)
maximum wet bulb
Maximum 9840 feet (3000 meters) at 104˚F (40˚C)
-200 feet to 5900 feet (-60 meters to 1800 meters) at
104˚F (40˚C)
5900 feet to 13100 feet (1800 meters to 4000 meters)
at 86˚F (30˚C)
Nonoperating
–40˚F to 158˚F (–40˚C to 70˚C)
5% to 93% noncondensing
100.4˚ (37.7˚C) maximum wet
bulb
Maximum 39370 feet (12000
meters)